Skip to main content

High-Rise Residential Buildings: 18 Metres or Seven Storeys

Requirements for high-rise residential buildings in England - defined as at least 18 metres in height or at least 7 storeys. Secure information box, external-wall information, wayfinding, firefighters' lift checks, and the separate residential evacuation plans regime.

Written for England. Check the position if your property is elsewhere in the UK.

11 min

Key takeaways

  • A high-rise residential building is one that is at least 18 metres high or at least 7 storeys, applying the statutory definitions and measurement rules - not simply 'over 18 metres'
  • All duties for buildings more than 11 metres high also apply (fire door checks), plus the additional high-rise duties below
  • Additional duties: secure information box, external-wall information, floor/building plans, monthly firefighters' lift and essential firefighting equipment checks, and wayfinding signage
  • A separate regime - the Residential Evacuation Plans Regulations 2025 - applies to specified residential buildings from 6 April 2026 and replaces the old self-identification PEEP approach
  • Do not assume a 'stay put' strategy applies solely because of a building's height or type - follow the building's current, validated evacuation strategy

The High-Rise Threshold

For the Fire Safety (England) Regulations 2022, do not use 'over 18 metres' as the sole trigger. A high-rise residential building is determined using the statutory test, including the at least 18 metres or at least 7 storeys alternatives. Apply the legislation's definitions and measurement provisions.

Duties are cumulative

A high-rise residential building must comply with all requirements that apply to buildings more than 11 metres high (quarterly communal fire door checks and best-endeavours annual flat entrance door checks) plus the additional requirements described below. Wayfinding signage and firefighters' lift/equipment duties apply at this tier, not merely because a building exceeds 11 metres.

Additional Requirements for High-Rise Residential Buildings

In addition to the duties for buildings more than 11 metres high, a high-rise residential building has these additional duties under the Fire Safety (England) Regulations 2022:

1. External Wall Information

Responsible persons must provide the fire and rescue service with information about the materials in external walls. This helps firefighters assess the risks and make informed decisions during an incident.

What External Wall Information to Provide

  • Construction details: Information about the external wall system and materials used.
  • Cladding: Details of any cladding, including type and manufacturer where known.
  • Insulation: Type of insulation materials used in the wall build-up.
  • Remediation work: Details of any remediation work carried out or planned.

2. Floor and Building Plans

Up-to-date floor plans and building plans must be maintained and made available to the fire and rescue service electronically. These are essential for firefighters to navigate the building and manage incidents effectively.

Plan Requirements

  • Floor layouts: Plans showing the layout of each floor, including flat positions.
  • Escape routes: Clear identification of all escape routes and exits.
  • Key locations: Fire safety equipment, risers, evacuation lifts, and control rooms.
  • Up-to-date: Plans must reflect the current building configuration.

3. Secure Information Box

A secure information box must be installed in a location accessible to the fire and rescue service. This provides firefighters with essential information on arrival.

Information Box Contents

  • Building and floor plans: Copy of up-to-date floor plans.
  • Contact details: Emergency contact information for responsible person.
  • Resident-specific information: Handled in accordance with the Residential Evacuation Plans Regulations 2025 and data-protection law. Information specified by those Regulations is provided to the fire and rescue authority only in accordance with that regime, including its explicit-consent requirement. Follow the fire and rescue authority's specified method, including use of the secure information box where applicable.
  • Key fire safety information: Relevant information about fire safety systems and arrangements.

4. Wayfinding Signage

Floor identification signage must be installed in stairwells. This helps firefighters and residents orientate themselves within the building, particularly during an emergency.

Signage Requirements

  • Location: Visible on every floor within stairwells and landing areas.
  • Content: Clear floor number identification.
  • Visibility: Easy to read in normal and emergency lighting conditions.

5. Firefighters' Lifts and Essential Firefighting Equipment

Where present, lifts intended for use by firefighters and essential firefighting equipment must be checked at least monthly, and qualifying faults or outages must be reported to the fire and rescue service.

Residential Evacuation Plans Regulations 2025

From 6 April 2026, the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 impose additional duties for specified residential buildings. See the dedicated Residential Evacuation Plans guide.

These Regulations require the responsible person to use reasonable endeavours to identify relevant residents whose ability to evacuate without assistance is compromised by a cognitive or physical impairment or condition - the process does not depend solely on residents volunteering this information. Following identification, the responsible person must offer a person-centred fire risk assessment, discuss reasonable and proportionate mitigation, and record an agreed approach in a written emergency evacuation statement. The assessment, mitigation and statement must be reviewed within the periods specified by the Regulations, including an annual review requirement.

Evacuation Strategy

State and follow the building's current, validated evacuation strategy. Do not infer 'stay put' or simultaneous evacuation solely from building height or generic building type. The fire risk assessment, fire strategy and relevant building information must support the strategy, and any change of strategy must be managed accordingly.

Stay Put and Simultaneous Evacuation

Where a building operates a "stay put" strategy, that strategy relies on the building's fire safety design to contain fire and smoke, and must be supported by adequate measures including working fire doors, fire compartmentation and fire detection. Where a simultaneous evacuation strategy applies instead - including where relevant under the Residential Evacuation Plans Regulations 2025 - follow that strategy. If deficiencies mean the current strategy is not safe, obtain competent advice and manage the change formally.

Additional responsible-person duties in force from 1 October 2023

Section 156 of the Building Safety Act 2022 changed the Fire Safety Order regime in England from 1 October 2023.

A responsible person must now record the fire risk assessment in full and record the fire-safety arrangements, irrespective of the number of employees. Where another person or organisation is engaged to undertake or review the fire risk assessment, record that person's identity or, as applicable, the organisation's identity.

The responsible person must also keep the required responsible-person information current and comply with applicable information-sharing and co-operation duties. This includes taking reasonably practicable steps to identify other responsible persons who share or have duties in respect of the premises and, where relevant, Accountable Persons under the Building Safety Act regime; the relevant parties must exchange the required information and co-operate.

Where responsibility for premises changes, the outgoing responsible person must provide the incoming responsible person with relevant fire-safety information required by the legislation. For buildings containing two or more sets of domestic premises, responsible persons also have additional duties to provide relevant fire-safety information to residents in an understandable form.

These changes were not limited to holiday lets or high-rise residential buildings.

Meeting a recommendation is not automatically compliance

Meeting an individual recommendation does not by itself establish compliance with the Fire Safety Order. Measures must be appropriate to the premises, persons at risk and findings of the suitable and sufficient fire risk assessment.

Frequently Asked Questions

  • +What if I don't know what's in the external walls?
    You may need to commission an intrusive survey to determine external wall composition. This is particularly important post-Grenfell and may already have been done as part of building safety assessments. If you cannot determine the composition, record this and seek professional advice.
  • +What if a resident does not tell me they need help to evacuate?
    You must use reasonable endeavours to identify relevant residents under the Residential Evacuation Plans Regulations 2025 - the duty does not depend solely on a resident volunteering the information. Reasonable endeavours can include direct communication, accessible information and working with support services, but you cannot force a resident to disclose details they do not wish to share.
  • +How should I handle resident evacuation data under data protection law?
    Health and disability information is sensitive personal data. The Residential Evacuation Plans Regulations 2025 preserve data-protection obligations, and a generic 'legitimate interests' label should not be applied automatically to this information. Take specific UK GDPR and Data Protection Act advice on the lawful basis and any special-category-data condition that applies, in addition to complying with the explicit-consent requirement for information shared with the fire and rescue authority.

Next Steps

Ensure you have all required documentation in place for your high-rise building, including your building emergency evacuation plan.

Ask us about your building

Sources

Need a fire risk assessment?

Tell us about the building and what you need, and we’ll let you know how we can help.